Cooling a High-Power UV LED Curing Line with the CW-6800 Water Chiller
UV LED curing has replaced mercury lamps on most cosmetic packaging printing lines, but the lamp head is only half of the system. A water cooled UV LED array rejects a large share of its input power as heat at the chip junction, and that heat has to leave the system continuously. This case describes how the CW-6800 industrial water chiller was specified for a cosmetic bottle printing line, and what changed once the cooling loop was sized correctly.
The Challenge
The customer runs a linear UV printing line for cosmetic bottles and tubes. Several lamp heads are mounted over the conveyor, curing UV ink and varnish on cylindrical containers at short cycle times. The line had two recurring problems:
- Output drift through the shift. As the lamp head heats up, irradiance falls and the cure becomes inconsistent between the first and last bottles of a run.
- Heat reaching the substrate. Thin-walled PET bottles began to deform when the lamp head ran hot, forcing the operator to slow the conveyor and cut throughput.
The original cooling arrangement was undersized: a small chiller with limited flow and no head pressure margin. It could not hold a stable set point once more than one lamp head was running.
Sizing the Cooling Loop
Two numbers decide whether a chiller will hold a UV LED lamp head stable: cooling capacity and flow at the required lift. Our engineers worked backwards from the lamp head input power and the mounting height above the line.
| Requirement | Line Condition | CW-6800 Capability |
|---|---|---|
| Heat rejection | Multiple high power UV LED lamp heads running continuously | 7.5KW / 17510-17640 Btu/h / 7420-7448 Kcal/h |
| Coolant flow | Parallel feed to several lamp heads | 80L/min (4.8 m3/h) max flow |
| Head pressure | Lamp heads mounted above the line, long hose run | 28m max lift, no booster pump needed |
| Temperature stability | Cure dose must not drift during a shift | +/-0.5 C accuracy at 12-14A working current |
| Buffer volume | Short interruptions during hose changes | 15L tank |
The Solution
The CW-6800 was installed as a closed loop: coolant leaves the 15L tank, passes through the lamp head water jacket and returns to the chiller. The unit's 3.0KW compressor and capillary tube throttling hold the set point without hunting, and the 10mm / 20mm inlet and outlet options allowed the existing hose set to be reused rather than replaced.
Two safeguards proved decisive in daily operation. Compressor over-current protection and flow alarm shut the chiller down before a blocked hose can cook a lamp head, and the over-temperature alarm gives the operator a warning instead of a sudden line stop. On a line where a replacement lamp head is a significant cost, that protection pays for itself.
The physical layout mattered too. At 68 x 58 x 95cm and 90kg net, the unit fits beside the press without taking floor space from the operator, and the castors let maintenance move it for hose access.
Results
- Stable cure across the shift. With the set point held to +/-0.5 C, irradiance stayed flat from the first bottle to the last, so the operator no longer re-ran rejected bottles at the end of a run.
- Line speed restored. Because the substrate stopped picking up radiant heat, conveyor speed returned to the original setting instead of being throttled to protect thin-walled bottles.
- Fewer unplanned stops. Flow and over-temperature alarms caught a partially blocked hose during scheduled maintenance instead of mid-production.
- One chiller, several heads. The 80L/min flow and 28m lift allowed a single CW-6800 to feed all lamp heads on the line, simplifying the installation and the spare parts list.
Lessons for Similar Projects
Three points apply to almost every UV LED curing retrofit:
- Size on heat, not on lamp count. Add up the total input power of the lamp heads and confirm the chiller's cooling capacity with margin.
- Check lift before flow. A chiller can be rated for high flow and still starve a lamp head mounted several metres above it.
- Match frequency to the local supply. The CW-6800 is available as AH, AI and AN (50Hz) and BH, BI and BN (60Hz) variants, with pump power rising from 0.05KW to 0.76KW across the range.